# Elevator status for 77 W Wacker Dr

> Live status is not available for 77 W Wacker Dr. Outage counts come from compliance inspection records, not a real-time feed.

Canonical: <https://www.elevatoruptime.com/building/0de99bfc-28ad-4b5a-a53d-cf5cd40c89e3>
Location: Chicago, US

## Status right now

36 open inspection records on file.

## Reliability

- **Inspection records in last 365 days:** 0

Uptime and time-to-fix are not published for this building because the only data source is compliance inspection records, not a live feed.

## Active outages

- **Elevator out** — earliest started 4y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1310: MAINT PLATFORM LIFT | Inspector: FAILED DUE TO INCOMPLETE CONTRUCTION & NO SAFETIES | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 4y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE ESCUSSION TUBES IN ALL HOISTWAY DOORS ELEVATOR #H16 & ALL OTHER HOISTWAY DOORS IN THE BUILDING | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 4y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PATCH ALL GAPS AT THE FLOOR LEVEL FRONT OF THE BLIND HOISTWAY MULTIPLE FLOORS. MAINTAIN FIRE RATING THROUGH OUT THE HOISTWAY ELEVATOR #H16 | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 4y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #F2.LABEL MAINLINE AND 110 VAC DISCONNECTS WITH CIRCUIT FEED LOCATION(S). | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 4y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #F2, PROVIDE AUXILARY CONTACT FOR BATTERY RESCUE AND TEST. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 4y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: TEST EMERGENCY POWER OPERATION FOR FINAL. ALL UNITS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 4y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: VERIFY GROUND/BOND FOR MAINLINE DISCONNECTS. ALL UNITS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 4y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: TEST ALL FAID'S FOR FINAL. ALL ELEVATORS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 4y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE FIRE RATED PIT ACCESS DOORS. PROVIDE ELECTRIC CONTACT AND WINDOWS FOR SAME. CARS H15 AND H16. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 4y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE LABEL FOR MAINLINE AND 110 VAC DISCONNECTS WITH ELEVATOR NUMBER AND CIRCUIT FEED LOCATION FOR FINAL. ALL ELEVATORS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 4y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE CODE COMPLIANT ELECTRICAL BOND/GROUND FOR MAINLINE DISCONNECT. CAR H15 | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1111: MAINTAIN OR REPAIR HYDRO ELEVA | Inspector: PROVIDE IDENTIFICATION OF DISCONNECT, TANK, CONTROLLER IN THE MACHINE ROOM, PIT, TOE GUARD, CROSS HEAD OF ELEVATOR #P1. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1111: MAINTAIN OR REPAIR HYDRO ELEVA | Inspector: PROVIDE PROTECTIVE PADDING ON UNI-STRUT AND TRAY HANGING IN THE MACHINE ROOM OF ELEVATOR #P1. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1111: MAINTAIN OR REPAIR HYDRO ELEVA | Inspector: RE-ROUTE A/C CONDENSATION UNIT DRAIN PIPE IN THE MACHINE ROOM OF ELEVATOR #P1. CURRENTLY AT THE HEIGHT OF 5'3" ACROSS THE MAIN MAINTENANCE PATH OF THE ROOM | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1111: MAINTAIN OR REPAIR HYDRO ELEVA | Inspector: PATCH HOISTWAY FOR ELEVATOR # SI | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPLACE HOIST ROPES ELEVATORS # H13, # H14, # H16, &  #H18 | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPAIR/REPLACE WORN BEARINGS ON SECONDARY SHEAVES OR MACHINES ON ELEVATORS # H11, # H14, # H16, # H17, #H18,  & # H19 | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPLACE GOVERNOR ROPE DAMAGED DURING ACCEPTANCE TESTING | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROPERLY MOUNT COMPONENTS IN THE CONTROLLER OF ELEVATOR #M11 | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE CONVENIENCE GFCI OUTLETS IN ALL MACHINE SPACES IN MACHINE ROOMS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE CAR NUMBERS ON PIT ACCESS DOORS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE ADDITIONAL LIGHTING WITH MECHANICAL PROTECTION THROUGH OUT ALL MACHINE ROOMS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE DRIP PANS UNSER ALL PLUMBING, CHILLER WATER PIPES, REPAIR LEAKS IN THE MID-RISE MACHINE ROOM FOR ELEVATOR #M9(OLD #9) | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE LIGHTING WITH MECHANICAL PROTECTION THROUGH OUT ALL MACHINE ROOMS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE ESCUSSIONS FOR HOISTWAY ACCESS ON ALL HOISTWAY DOORS INCLUDING LOBBY DOORS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 7y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PATCH/FIRE CAULK HOISTWAY OF ELEVATOR #F1 ALL BEAM INTERSECTIONS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 7y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE METAL SUMP COVER. CAR F1 | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 7y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE SUMP COVER. CAR F1 | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 7y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: TEST EMRGENCY POWER OPERATION. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 7y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: TEST F.A.I.D.'S | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 7y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: IDENTIFY MAIN & EMERGENCY BRAKE. ALL CARS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 7y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE PERMANENT MEANS (LADDER NO ROOM FOR A PLATFORM) IN PIT TO ACCESS BOTTOM OF CAR. CAR F1 | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 7y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE PERMANENT MEANS IN PIT TO ACCESS BOTTOM OF CAR. CAR F1 | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 7y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: IDENTIFY MAIN & EMERGENCY BRAKE. ALL CARS, ALL MACHINE ROOMS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 7y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: TEST EMRGENCY POWER OPERATION.UPON THE COMPLETION OF THE MODERNIZATION | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 7y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: TEST FIRE SEVICE PHASE I & II AND F.A.I.D.'S AT THE COMPLETION OF MODERNIZATION WORK | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr

## Recent history (last 90 days)

No inspection records in the last 90 days.

## Service contractor

Service provider not yet verified. If you maintain these elevators or know who does, submit a tip at <https://www.elevatoruptime.com/building/0de99bfc-28ad-4b5a-a53d-cf5cd40c89e3#contractor>

## Data sources

- **Chicago DOB inspections** — 85 records

## Common questions

### Is the 77 W Wacker Dr elevator working right now?

Live status is not published for 77 W Wacker Dr because the only data source is compliance inspection records. 0 open or recent records are on file.

### How do I report a broken elevator at 77 W Wacker Dr?

Use the report form at https://www.elevatoruptime.com/report. It takes about 15 seconds and no account is required.

## Report or correct