# Elevator status for 6425 S Lowe Ave

> Live status is not available for 6425 S Lowe Ave. Outage counts come from compliance inspection records, not a real-time feed.
> 
> 2 inspection records in the last 365 days.

Canonical: <https://www.elevatoruptime.com/building/141fb2b1-562c-4c5c-b75e-06e0764a41c6>
Location: Chicago, US

## Status right now

52 open inspection records on file.

## Reliability

- **Inspection records in last 365 days:** 2

Uptime and time-to-fix are not published for this building because the only data source is compliance inspection records, not a live feed.

## Active outages

- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE CANT/ BEVEL THROUGHOUT HOISTWAY BETWEEN CARS 2 AND 3 PER CODE (NOT LESS THAN 70 DEGREES). | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: FINALIAZE OPEN MODERNIZATION PERMIT NUMBER 101057168.SEE PERMIT FOR ADDITIONAL VIOLATIONS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: RESTORE ELEVATOR #3 TO SAFE OPERATION. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE CODE COMPLIANT FIRE RESISTANT DOOR LOCK WIRE AT ALL LANDINGS FOR CONSTRUCTION USE. ALL ELEVATORS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE PUSH/PULL TYPE STOP SWITCH IN PIT FOR ALL ELEVATORS PER CODE. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REMOVE ALL UNUSED/ ABANDONED PIPE(S) AND ELECTICAL BOXES FROM HOISTWAY AND ELEVATOR. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: TEST ALL FAID'S AN EMERGENCY POWER (IF APPLICABLE) FOR FINAL. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE PHONE LINE MONITORING PER CODE FOR ALL ELEVATORS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE DIAGRAM OF MAIN LANDING, DETAILING LOCATION OF ALL ELEVATORS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE CODE COMPLIANT FIRE RESISTANT DOOR LOCK WIRE AT ALL LANDINGS FOR CONSTRUCTION USE. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE PUSH/PULL TYPE STOP SWITCH IN PIT. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: INSTALL CAR TOP FAN. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPLACE DAMAGED HOISTWAY DOORS PER CODE AS NECESSARY DUE TO VANDALISM/ COMPROMISED FIRE RATING PRIOR TO PLACING CAR IN SERVICE FOR CONSTRUCTION USE. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: LABEL MAINLINE AND 110 VAC DISCONNECTS WITH ELEVATOR NUMBER AND CIRCUIT FEED LOACATION. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REMOVE ALL UNUSED/ ABANDONED PIPE(S) AND WIRES FROM HOISTWAY. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE CODE COMPLIANT BONDING/ GROUND FROM MAINLINE DISCONNECTS TO CONTROLLER AND MACHINERY FOR CONSTRUCTION USE. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE AND TEST FIRE SPEAKERS PER CODE. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE STRUCTURAL ENGINEERING REPORT REGARDING INSTALLATION OF ROPE GRIPPER. RETEST REQUIRED WITH 125 PERCENT LOAD FOR CONSTRUCTION USE. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: TEST ALL FAID'S. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE UPDATED FIRE EXTINGUISHER INSIDE MACHINE ROOM. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPAIR FIRE SERVICE PHASE I KEY SWITCH IN LOBBY. MUST RECALL ALL ELEVATORS IN SERVICE FOR PUBLIC. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPLACE DAMAGED HOISTWAY AND CAR DOORS PER CODE AS NECESSARY. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPAIR ELEVATOR #1. OUT OF SERVICE AT TIME OF INSPECTION. PENDING MODERNIZATION. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPAIR/REPLACE MISSING SIGHT GUARDS. ALL LANDINGS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: CLOSE OUT OPEN PERMIT NUMBERED 101057168. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPAIR ELEVATOR #3. RESTORE TO SAFE OPERATION. OUT OF SERVICE AT TIME OF INSPECTION. PENDING MODERNIZATION. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: UPDATE MAINTENANCE CONTROL PROGRAM LOGS AND FIRE SERVICE TEST LOGS BY LICENSED ELEVATOR CONTRACTOR. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPAIR ELEVATOR #3. RESTORE TO SAFE OPERATION. OUT OF SERVICE AT TIME OF INSPECTION. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: VERIFY ALL DOOR GIBS AND FIRE STOPS. ALL LANDINGS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 4y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: RESTORE ALL ELEVATORS TO FULL AUTOMATIC OPERATION. CARS 1 AND 2 OPERATING ON INDEPENDENT SERVICE OPERATION ONLY. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 4y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE FIRE GIB ON HOISTWAY DOORS. ALL OPENINGS, ALL UNITS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: LOCK/SECURE CAR TOP ESCAPE HATCH. ALL UNITS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE ANTI SPIN DEVICE ON ROPE SHACKLES ON CAR AND COUNTERWEIGHT. CAR #3. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPAIR EMERGENCY LIGHT. CAR #2. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPLACE MISSING DOOR LOCK COVERS. CLOSE OPEN ELECTRICAL BOXES. ALL UNITS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPLACE MISSING FACIA/TOE GUARD. CAR #1. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPAIR EMERGENCY LIGHT AND BELL. CAR #1 | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPAIR/REPLACE CAR DOOR RESTRICTORS. ALL UNITS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REMOVE EXCESS TAPE FROM GATE SWITCH ROLLER(S). PROVIDE PROPER ROLLER FOR GATE SWITCH OPERATION. ALL UNITS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REMOVE DEBRIS FROM PIT/CLEAN PIT. AL UNITS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 15y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1111: MAINTAIN OR REPAIR HYDRO ELEVA | Inspector: PROPERLY PROGRAAM ELEVATOR EMERGENCY PHONE TO 24HR ANSWERING SOURCE ELEVATORS # 1,2,3 | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 15y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1111: MAINTAIN OR REPAIR HYDRO ELEVA | Inspector: PERFORM ANNUAL RELIEF VALVE AND PRESSURE TEST | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 21y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV0279: REP/REPL CAR FIRE KEY SW PASS | Inspector: ALL ELEVATORS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 21y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV0258: REP/REPL DEF CWT BUFFER PASS | Inspector: ELEVATOR #1. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 21y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV0256: REP/REPL DEF BUFFER PASS | Inspector: ALL ELEVATORS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 21y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV0040: POST CURRENT CERTIF PASS ELE | Inspector: ALL ELEVATORS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 21y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV0254: REMOVE WATER FROM PIT PASS | Inspector: ALL CARS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 21y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV0252: REMOVE DEBRIS FROM PIT PASS | Inspector: ALL CARS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 21y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV0236: REPL DEF HOIST ROPES PASS | Inspector: ELEVATOR #1. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 21y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV0275: REP/REPL FIRE RECALL PASS | Inspector: ALL ELEVATORS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 21y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV0185: ILLUMINATE ELEV PIT | Inspector: ALL CARS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 21y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV0192: INST PROP RACEWAYS FOR WIRING | Inspector: ALL CARS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr

## Recent history (last 90 days)

No inspection records in the last 90 days.

## Service contractor

Service provider not yet verified. If you maintain these elevators or know who does, submit a tip at <https://www.elevatoruptime.com/building/141fb2b1-562c-4c5c-b75e-06e0764a41c6#contractor>

## Data sources

- **Chicago DOB inspections** — 173 records

## Common questions

### Is the 6425 S Lowe Ave elevator working right now?

Live status is not published for 6425 S Lowe Ave because the only data source is compliance inspection records. 2 open or recent records are on file.

### How do I report a broken elevator at 6425 S Lowe Ave?

Use the report form at https://www.elevatoruptime.com/report. It takes about 15 seconds and no account is required.

## Report or correct

- **Report a broken elevator or escalator:** <https://www.elevatoruptime.com/report>
- **Building owner or manager? Claim this listing:** <https://www.elevatoruptime.com/building/141fb2b1-562c-4c5c-b75e-06e0764a41c6#claim> — or email <mailto:info@elevatoruptime.com?subject=Claim%20building%3A%206425%20S%20Lowe%20Ave%20(141fb2b1-562c-4c5c-b75e-06e0764a41c6)>
- **Elevator service contractor? Claim your devices:** <https://www.elevatoruptime.com/building/141fb2b1-562c-4c5c-b75e-06e0764a41c6#claim-devices> — or send a tip by email <mailto:info@elevatoruptime.com?subject=Contractor%20tip%3A%206425%20S%20Lowe%20Ave%20(141fb2b1-562c-4c5c-b75e-06e0764a41c6)>

---
Site overview for agents: <https://www.elevatoruptime.com/llms.txt>