# Elevator status for 815 W 63rd St

> Live status is not available for 815 W 63rd St. Outage counts come from compliance inspection records, not a real-time feed.
> 
> 3 inspection records in the last 365 days.

Canonical: <https://www.elevatoruptime.com/building/4013e377-5969-42e4-aa85-1e1badd5df17>
Location: Chicago, US

## Status right now

26 open inspection records on file.

## Reliability

- **Inspection records in last 365 days:** 3

Uptime and time-to-fix are not published for this building because the only data source is compliance inspection records, not a live feed.

## Active outages

- **Elevator out** — earliest started 8mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: CATEGORY 5 TEST PAST DUE. ALL ELEVATORS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 11mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: EMERGENCY PHONE(S) NOT WORKING. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: CATEGORY 1 TEST PAST DUE. PROVIDE DOCUMENTATION. FREIGHT ELEVATOR #3- CODING. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: FRONT LOBBY ELEVATOR: REPAIR FIRE SERVICE OPERATION. VERIFY FIRE SERVICE PHASE II MANDATE. ELEVATOR DOES NOT RECALL WHEN PHASE II IS TRUNED OFF. ELEVATOR CAN OPERATE WHEN ON DOOR HOLD MODE. PERMIT REQUIRED. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: CATEGORY 1 TEST PAST DUE. PROVIDE DOCUMENTATION. FREIGHE ELEVATOR #3- CODING. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: FRONT LOBBY ELEVATOR: REPAIR FIRE SERVICE OPERATION. VERIFY FIRE SERVICE PHASE II MANDATE. ELEVATOR DOES NOT RECALL WHEN PHASE II IS TRUNED OFF. ELEVATOR CAN OPERATE WHEN ON DOOR HOLD MODE. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: CATEGORY 1 TEST PAST DUE. PROVIDE DOCUMENTATION. FREIGHE ELEVATOR #3- CODING. NOTE: NEXT CATEGORY 1 TEST DUE FOR CARS 1 AND 2 DUE BY 1-20-2024. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REPAIR EMERGENCY PHONE TO BRAODCAST BUILDING ADDRESS AND ELEVATOR CAR NUMBER. ALL ELEVATORS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: FRONT LOBBY ELEVATOR: REPAIR FIRE SERVICE OPERATION. VERIFY FIRE SERVICE PHASE II MANDATE. ELEVATOR DOES NOT RECALL WHEN PHASE II IS TRUNED OFF. ELEVATOR CAN OPERATE WHEN ON DOOR HOLD MODE. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ELEVATOR #1: PROVIDE 2HR FIRE RATED CAULK FOR BUTTON BOXES IN HOISTWAY WHERE NEEDED | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REAR EAST #2: ALARM DOES NOT WORK | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ELEVATOR #5 (2ND FL REAR): BRING ELEVATOR TO WORKING CONDITION OR PULL PERMIT TO DECOMISSION ELEVATOR | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ELEVATOR #1 AND #2:  PROVIDE ADEQUATE LIGHTING IN MACHINE ROOM AND PIT | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PREVIOUS VIOLATION: (ELEVATOR #2)TWO-WAY COMMUNICATION DEVICE NOT WORKING PROPERLY | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PREVIOUS VIOLATION: (ELEVATOR #1) SIGNALING ALARM NOT FUNCTIONING PROPERLY. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ELEVATOR #1: SERVICE FIRE EXTINGUISHER IN MACHINE ROOM | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ELEVATOR #2: PROVIDE FIRE TABS ON HOISTWAY DOORS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ALL ELEVATORS: GIVE EACH ELEVATOR A UNIQUE ID. NUMBER ALL PIT, ELEVATOR C.O.P.S, MACHINE ROOM EQUIPMENT WITH UNIQUE ID. (EXAMPLE #1-#5 OR A-E) | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ALL ELEVATORS: GIVE EACH ELEVATOR A UNIQUE ID. NUMBER ALL PIT EQUIPMENT, ELEVATOR C.O.P.S, MACHINE ROOM EQUIPMENT WITH UNIQUE ID. (EXAMPLE #1-#5 OR A-E) | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ELEVATOR #2: EMERGENCY PHONE NOT OPERABLE DURING INSPECTION | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ELEVATOR #1 (REAR WEST): BRING ELEVATOR TO WORKING CONDITION OR PULL PERMIT TO DECOMISSION ELEVATOR | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PREVIOUS VIOLATION: (REAR EAST #2) SIGNALING ALARM NOT FUNCTIONING PROPERLY. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ELEVATOR #1: PROVIDE INNER AND OUTER DOOR STRAPS ON FREIGHT DOORS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: REAR EAST #2: PROVIDE INNER AND OUTER DOOR STRAPS ON FREIGHT DOORS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ELEVATOR #1: PROVIDE SIGNAGE FOR MACHINE ROOM DOOR | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 6y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PREVIOUS VIOLATION: (ELEVATORS #1 & #2) PROVIDE ANNUAL AND 5 YEAR TEST/TAGS. (CAT1/CAT5) | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr

## Recent history (last 90 days)

No inspection records in the last 90 days.

## Service contractor

Service provider not yet verified. If you maintain these elevators or know who does, submit a tip at <https://www.elevatoruptime.com/building/4013e377-5969-42e4-aa85-1e1badd5df17#contractor>

## Data sources

- **Chicago DOB inspections** — 81 records

## Common questions

### Is the 815 W 63rd St elevator working right now?

Live status is not published for 815 W 63rd St because the only data source is compliance inspection records. 3 open or recent records are on file.

### How do I report a broken elevator at 815 W 63rd St?

Use the report form at https://www.elevatoruptime.com/report. It takes about 15 seconds and no account is required.

## Report or correct

- **Report a broken elevator or escalator:** <https://www.elevatoruptime.com/report>
- **Building owner or manager? Claim this listing:** <https://www.elevatoruptime.com/building/4013e377-5969-42e4-aa85-1e1badd5df17#claim> — or email <mailto:info@elevatoruptime.com?subject=Claim%20building%3A%20815%20W%2063rd%20St%20(4013e377-5969-42e4-aa85-1e1badd5df17)>
- **Elevator service contractor? Claim your devices:** <https://www.elevatoruptime.com/building/4013e377-5969-42e4-aa85-1e1badd5df17#claim-devices> — or send a tip by email <mailto:info@elevatoruptime.com?subject=Contractor%20tip%3A%20815%20W%2063rd%20St%20(4013e377-5969-42e4-aa85-1e1badd5df17)>

---
Site overview for agents: <https://www.elevatoruptime.com/llms.txt>