# Elevator status for 400 E Randolph St

> Live status is not available for 400 E Randolph St. Outage counts come from compliance inspection records, not a real-time feed.
> 
> 39 inspection records in the last 365 days.

Canonical: <https://www.elevatoruptime.com/building/6a68a0c6-2c9a-4d32-a164-3d2bb4d12caf>
Location: Chicago, US

## Status right now

54 open inspection records on file.

## Reliability

- **Inspection records in last 365 days:** 39

Uptime and time-to-fix are not published for this building because the only data source is compliance inspection records, not a live feed.

## Active outages

- **Elevator out** — earliest started 3mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: CAR G: PROVIDE UPDATED COUNTERWEIGHT GOVERNOR DATA TAG | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 3mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: CAR G: COMPLETE THE FOLLOWING TESTING FOR TEMP USE - COUNTERWEIGHT DROP TEST, ETS (EMPTY AND FULL), PHASE I/II, TESTING OF STOP SWITCH IN SECONDARY | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 3mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ALL ELEVATORS WITH SECONDARIES: INSTALL GAURDS AROUND HOIST AND GOVERNOR ROPES AS REQUIRED | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 3mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: CAR G: INSTALL COUUNTERWEIGHT RUNBY SIGNAGE IN PIT | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 3mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: CAR G: PROVIDE LOBBY ESCUTCHEON | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 3mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: CAR F: COMPLETE FASCIA INSTALL FROM LOWEST LANDING TO 4TH FLOOR. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 3mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: CAR G: INSTALL ALL ROLL PINS ON HOIST MOTOR BED PLATE AS REQUIRED | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 3mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: MACHINE ROOM OF D-I: FIRE RATE WHERE REQUIRED. PLUG/ COVER ALL HOLES THROUGH MACHINE ROOM FLOOR AND CEILING. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: INSTALL "IN CASE OF FIRE" SIGNAGE AT EACH LANDING. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: A THRU C: REMOVE UNUSED STRAPS, NAILS AND ANCHORS FROM MACHINE ROOM CEILING. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: A THRU C: PROVIDE CODE COMPLIANT COUNTERWEIGHT GAURDS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: C: RELOCATE AC LINES IN MACHINE ROOM OR PROVIDE SENSORED DRIP PANS UNDER EXISTING AC LINES. FIRE CAULK WHERE AC LINES PENETRATE THROUGH MACHINE ROOM CEILING. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: C: PROGRAM PI TO MATCH FLOOR DESIGNATIONS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 9mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: D ELEVATOR: PATCH HOLE IN FLOOR OF SECONDARY. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 9mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: D ELEVATOR: SECURE/ REPAIR HOIST CABLE TAILS IN OVERHEAD. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 9mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: D: CAULK BROKEN HOISTWAY BRICK BETWEEN 8TH AND 9TH LANDING | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 9mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: D: PROVIDE SENSORED DRIP PAINS OVER ALL ELEVATOR EQUIPMENT IN MACHINE ROOM THAT IS UNDERNEAT ALL DRAINS AND WATER PIPES. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 9mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: D: CORRECT C.O.P. IN-CAR BUTTON FLOOR SELECTION (6TH LANDING IS MISSING) | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 9mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: D: PROVIDE SECONDAY ACCESS DOOR WITH GROUP I SECURITY AND WARNING LABEL | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 9mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: D: INSTALL ALL TROUGHT COVERS IN HOISTWAY AND MACHINE ROOM | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 9mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: CARS D - I: PROVIDE SENSORED DRIP PAINS OVER ALL ELEVATOR EQUIPMENT IN MACHINE ROOM THAT IS UNDERNEATH ALL DRAINS AND WATER PIPES. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 9mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: D: COVER HOLES IN MACHINE ROOM AND SECONDARY FLOOR | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 9mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: D: PROVIDE TOP ACCESS COVER | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 9mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ALL ELEVATORS: INSTALL ALL TROUGH AND JUNCTION BOX COVERS IN HOISTWAY AND MACHINE ROOM | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 9mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: D: MOVE SECONDAY STOP SWITCH ADJACENT TO MACHINE AND LABEL | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 9mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: D: REMOVE UNUSED PIPE IN HOISTWAY | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 10mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: A:ADD COTTER PINS TO RODS ON CWT | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 10mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: A:PROVIDE MANUFACTURES DATA TAG ON CWT BUFFER | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 10mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: A:RE-ANCHOR MACHINE BASE AS NEEDED | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 10mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ALL MACHINE ROOMS: PROVIDE GFCI OUTLETS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 10mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: A:INSTALL ALL HOISTWAY COVERS (TROUGH AND 1900 BOXES) | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 10mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ALL MACHINE ROOMS: PROVIDE MOUNTED ABC FIRE EXTINGUISHER | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: F: PROVIDE TOC DATA PLATE, CODE DATA PLATE, CABLE DATA PLATES FOR GOVERNOR, CAR, AND COMPS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1111: MAINTAIN OR REPAIR HYDRO ELEVA | Inspector: F: PROVIDE PIT GUARDING BETWEEN ELEVATOR AT 4TH LANDING WHERE THERE IS A DIFFERENCE IN PIT DEPTHS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: F: PROVIDE COUNTERWEIGHT ANTI-ROTATION DEVICE | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ALL ELEVATORS: PROVIDE TOC DATA PLATE, CODE DATA PLATE, CABLE DATA PLATES FOR GOVERNOR, CAR, HOIST AND COMPS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE SELF-CLOSING SELF-LOCKING SECONDARY DOORS WITH GROUP I SECURITY FOR ALL SECONDARY ACCESS DOORS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ALL ELEVATORS: PROVIDE LANDING IDENTIFICATION ON HOISTWAY DOORS AT EACH LANDING | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: B ELEVATOR: PROVIDE A 3000 GAL/HR CAPACITY SUMP WITH CODE COMPLIANT PLUMBING CODE SECURED SUMP PUMP GRATING IN PIT | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: B ELEVATOR: PROVIDE EMERGENCY PHONE LINE AND TEST WITHOUT 110V POWER ON | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: B ELEVATOR: PROVIDE GUARD BETWEEN PIT PER ASME A17.1 2016 2.2.3.1 | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ALL ELEVATORS: PROVIDE KICK ANGLES ON CARTOP AND FINISH INSTALLING TOP OF CAR BARRICADE | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: B ELEVATOR: CAULK HOISTWAY SIDE OF FRAMES WHERE STOPS HAVE BEEN ADDED. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE "GAIN CONTROL/SWITCH ACTIVATED" PIT DOOR SIGNAGE ON ALL SWITCHED PIT DOORS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ALL MACHINE ROOMS: CAP ALL UNUSED HOLES IN FLOOR AND REMOVE UNUSED OVERHEAD PIPES/STRAPS/RODS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: B ELEVATOR: PROVIDE KICK ANGLES ON CARTOP AND FINISH INSTALLING TOP OF CAR BARRICADE | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE PIT DOOR SIGN ON OUTER PIT DOOR AND EACH INDIVIDUAL PIT DOOR WITH ELEVATOR ID. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ALL MACHINE ROOMS: PROVIDE MACHINE ROOM DOOR SIGNS WITH ELEVATOR IDENTIFICATION | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ALL ELEVATORS WITH COMP CHAINS: PROVIDE RED/WHITE DIAGONAL STRIPES UNDER COMP CHAINS IN PIT AND PROVIDE COUNTERWIGHT RUNBY SIGNS WITH "DANGER COUNTERWEIGHT" SIGNS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: A AND B ELEVATOR: PROVIDE GUARD BETWEEN PIT PER ASME A17.1 2016 2.2.3.1 | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: B ELEVATOR: PROVIDE TOP OF CAR DATA AND CODE DATA PLATES | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ALL PIT DOORS: PROVIDE SELF-LOCKING PIT DOORS. KEY MUST NOT HABE THE ABILITY TO KEEP DOOR UNLOCKED. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ALL ELEVATORS WITHOUT COMP CHAINS: PROVIDE PIT COUNTERWEIGHT GUARDS WITH RUNBY SIGNAGE | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 8y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: (AUDIT) PROVIDE TOP OF CAR HANDRAILS IF CLEARANCE ALLOWS. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr

## Recent history (last 90 days)

No inspection records in the last 90 days.

## Service contractor

Service provider not yet verified. If you maintain these elevators or know who does, submit a tip at <https://www.elevatoruptime.com/building/6a68a0c6-2c9a-4d32-a164-3d2bb4d12caf#contractor>

## Data sources

- **Chicago DOB inspections** — 74 records

## Common questions

### Is the 400 E Randolph St elevator working right now?

Live status is not published for 400 E Randolph St because the only data source is compliance inspection records. 39 open or recent records are on file.

### How do I report a broken elevator at 400 E Randolph St?

Use the report form at https://www.elevatoruptime.com/report. It takes about 15 seconds and no account is required.

## Report or correct

- **Report a broken elevator or escalator:** <https://www.elevatoruptime.com/report>
- **Building owner or manager? Claim this listing:** <https://www.elevatoruptime.com/building/6a68a0c6-2c9a-4d32-a164-3d2bb4d12caf#claim> — or email <mailto:info@elevatoruptime.com?subject=Claim%20building%3A%20400%20E%20Randolph%20St%20(6a68a0c6-2c9a-4d32-a164-3d2bb4d12caf)>
- **Elevator service contractor? Claim your devices:** <https://www.elevatoruptime.com/building/6a68a0c6-2c9a-4d32-a164-3d2bb4d12caf#claim-devices> — or send a tip by email <mailto:info@elevatoruptime.com?subject=Contractor%20tip%3A%20400%20E%20Randolph%20St%20(6a68a0c6-2c9a-4d32-a164-3d2bb4d12caf)>

---
Site overview for agents: <https://www.elevatoruptime.com/llms.txt>