# Elevator status for 21 E Bellevue Pl

> Live status is not available for 21 E Bellevue Pl. Outage counts come from compliance inspection records, not a real-time feed.
> 
> 8 inspection records in the last 365 days.

Canonical: <https://www.elevatoruptime.com/building/6b0ca3b6-da45-4232-bd5d-7207dfb70974>
Location: Chicago, US

## Status right now

20 open inspection records on file.

## Reliability

- **Inspection records in last 365 days:** 8

Uptime and time-to-fix are not published for this building because the only data source is compliance inspection records, not a live feed.

## Active outages

- **Elevator out** — earliest started 2mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1: TEST TRACTION LOSS FOR ELEVATOR AFTER HOIST CABLES ARE REPLACED. OTIS IS REQUIRED TO NOTIFY THE CITY THAT CABLE REPLACEMENT FOR ELEVATOR NEEDS TO BE RETESTED (COMPLAINT INSPECTION) | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1111: MAINTAIN OR REPAIR HYDRO ELEVA | Inspector: #5: RETURN ELEVATOR TO FULL OPERATION (COMPLAINT INSPECTION) | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1111: MAINTAIN OR REPAIR HYDRO ELEVA | Inspector: #5: PROVIDE SELF-LOCKING MACHINE ROOM DOOR WITH ELEVATOR/MACHINE ROOM DOOR SIGN.  (COMPLAINT INSPECTION) | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1111: MAINTAIN OR REPAIR HYDRO ELEVA | Inspector: #5: PROVIDE 5 YEARS OF MAINTENANCE/SERVICE/REPAIR RECORDS; FIRE TEST SHEETS; AND OIL USAGE LOGS.  (COMPLAINT INSPECTION) | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 7mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: AUDIT #4W: PROVIDE MINIMUM CLEARANCE BETWEEN COUNTERWEIGHT FRAME AND COUNTERWEIGHT BUFFER | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 7mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: AUDIT INSPECTION: CLOSE OPEN MODERNIZATION PERMIT THAT HAS HAD NO ACTION SINCE MAY 20, 2025. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 7mo ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: AUDIT INSPECTION: CLOSE OPEN MODERNIZATION PERMIT #101043792 THAT HAS HAD NO ACTION SINCE MAY 20, 2025. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1: PAINT CARTOP WOODEN CEILING | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1111: MAINTAIN OR REPAIR HYDRO ELEVA | Inspector: #1: PROGRAM EMERGENCY PHONE TO GIVE ELEVATOR ID TO OPERATOR. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1: PROVIDE ROPE DATA TAGS AND CODE DATA PLATE | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: ALL ELEVATORS: PROVIDE ADDITIONAL TOP OF CAR LIGHTING AND KICK ANGLES | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1: DEMARK PIT AREA UNDER COMP ROPES | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1: PPROVIDE MACHINE ROOM OVERHEAD VENT COVER | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 1y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE PERMANENT LOCKABLE LADDER TO ACCESS UNDERSIDE OF ELEVATOR FOR EACH PIT. | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE SIGNAGE ON THE MACHINE ROOM DOOR | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE FIRE ALARM INITIATING DEVICES FOR AUTOMATIC FIREMANS' RECALL | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE IDENTIFICATION ON THE CONTROLLER, MACHINE, GOVERNOR, DISCONNECTS, CROSSHEAD, AND PIT EQUIPMENT | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE A 48" TOE GUARD OR APPLY FOR AN ALTERATION TO CODE DUE TO EXISTING PIT DEPTH | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: PROVIDE AN ELEVATOR LOBBY CONTROL PANEL | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 2y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: SCHEDULE FIREMANS' RECALL TESTING OF PHASE I, PHASE II, FIRE ALARM INITIATING DEVICES | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr

## Recent history (last 90 days)

- 2026-09-01 → ongoing · Elevator · inspection record
- 2026-09-01 → ongoing · Elevator · inspection record
- 2026-09-01 → ongoing · Elevator · inspection record
- 2026-09-01 → ongoing · Elevator · inspection record

## Service contractor

Service provider not yet verified. If you maintain these elevators or know who does, submit a tip at <https://www.elevatoruptime.com/building/6b0ca3b6-da45-4232-bd5d-7207dfb70974#contractor>

## Data sources

- **Chicago DOB inspections** — 22 records

## Common questions

### Is the 21 E Bellevue Pl elevator working right now?

Live status is not published for 21 E Bellevue Pl because the only data source is compliance inspection records. 8 open or recent records are on file.

### How do I report a broken elevator at 21 E Bellevue Pl?

Use the report form at https://www.elevatoruptime.com/report. It takes about 15 seconds and no account is required.

## Report or correct

- **Report a broken elevator or escalator:** <https://www.elevatoruptime.com/report>
- **Building owner or manager? Claim this listing:** <https://www.elevatoruptime.com/building/6b0ca3b6-da45-4232-bd5d-7207dfb70974#claim> — or email <mailto:info@elevatoruptime.com?subject=Claim%20building%3A%2021%20E%20Bellevue%20Pl%20(6b0ca3b6-da45-4232-bd5d-7207dfb70974)>
- **Elevator service contractor? Claim your devices:** <https://www.elevatoruptime.com/building/6b0ca3b6-da45-4232-bd5d-7207dfb70974#claim-devices> — or send a tip by email <mailto:info@elevatoruptime.com?subject=Contractor%20tip%3A%2021%20E%20Bellevue%20Pl%20(6b0ca3b6-da45-4232-bd5d-7207dfb70974)>

---
Site overview for agents: <https://www.elevatoruptime.com/llms.txt>