# Elevator status for 1015 N Halsted St

> Live status is not available for 1015 N Halsted St. Outage counts come from compliance inspection records, not a real-time feed.

Canonical: <https://www.elevatoruptime.com/building/d7a11f99-ed95-460d-af40-b0ceed117725>
Location: Chicago, US

## Status right now

17 open inspection records on file.

## Reliability

- **Inspection records in last 365 days:** 0

Uptime and time-to-fix are not published for this building because the only data source is compliance inspection records, not a live feed.

## Active outages

- **Elevator out** — earliest started 4y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #2 ELEVATOR: FILL/COVER HOLE IN PIT TO REMOVE TRIP HAZARD | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 & #2 ELEVATOR: PROVIDE GFCI IN PIT AND MACHINE ROOM | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 & #2 ELEVATOR: PROGRAM PHONES TO GIVE CORRECT ELEVATOR IDENTIFICATION | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 & #2 ELEVATOR: PROVIDE ALTERNATE STOP SWITCH TO GAIN CONTROL OF CARTOP | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 & #2 ELEVATOR: PERFORM CAT1 AND CAT5 TESTS. PROVIDE TEST SHEET AND GOVERNOR TAGS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 & #2 ELEVATOR: PROVIDE FIRE CORRIDOR SIGNS ON EVERY LANDING | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 & #2 ELEVATOR: PROVIDE GOVERNOR DATA PLATE | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 & #2 ELEVATOR: PROVIDE CODE COMPLIANT PIT STOP SWITCH THAT MEETS THE 18" ABOVE SILL REQUIREMENT | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 ELEVATOR: PROVIDE PERMANENT NON COMBUSTIBLE ACCESS TO MACHINE ROOM IN ACCORDANCE WITH ASME A17.1 2016 8.11.2.1.2(B) CODE REQUIREMENTS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 & #2 ELEVATOR: PROVIDE CORRECT ELEVATOR IDENTIFICATION THAT MATCHES EACH ELEVATOR CAR STATION NUMBER (CAR 1 OR CAR 2). ID EACH WITH CORRECT IDENTIFICATION ON EACH: LANDING, PIT EQUIPMENT, MACHINE ROOM EQUIPMENT AND DISCONNECTS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 & #2 ELEVATOR: CAULK AROUOND HALL BUTTON BOXES AND PATCH HOISTWAY/MACHINE ROOM WITH 2HR FIRE RATED MATERIAL | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 & #2 ELEVATOR: PROVIDE PIT LIGHT SWITCH THAT IS ACCESSIBLE PRIOR TO ENTERING PIT AREA AND ADJACENT TO NEWLY INSTALLED PIT STOP SWITCH | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 & #2 ELEVATOR: PROVIDE ADA COMPLIANT FLOOR NUMBERS ON EACH JAMB ON EVERY LANDING | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 & #2 ELEVATOR: PROVIDE SELF-CLOSING/SELF-LOCKING MACHINE ROOM DOOR AND PROVIDE MACHINE ROOM DOOR SIGN | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 & #2 ELEVATOR: PROVIDE COUNTERWEIGHT RUNBY SIGN AND COMPLETE DATA | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 & #2 ELEVATOR: PROVIDE CODE COMPLIANT PIT LADDERS | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr
- **Elevator out** — earliest started 5y ago · Confirmed · source: Chicago DOB inspections
  > Chicago DOB EV violation EV1110: MAINTAIN OR REPAIR ELECT ELEVA | Inspector: #1 & #2 ELEVATOR: PROVIDE ELEVATOR CERTIFICATE FRAMES | inspection_status=FAILED violation_status=OPEN | evidence: https://data.cityofchicago.org/Buildings/Building-Violations/22u3-xenr

## Recent history (last 90 days)

No inspection records in the last 90 days.

## Service contractor

Service provider not yet verified. If you maintain these elevators or know who does, submit a tip at <https://www.elevatoruptime.com/building/d7a11f99-ed95-460d-af40-b0ceed117725#contractor>

## Data sources

- **Chicago DOB inspections** — 17 records

## Common questions

### Is the 1015 N Halsted St elevator working right now?

Live status is not published for 1015 N Halsted St because the only data source is compliance inspection records. 0 open or recent records are on file.

### How do I report a broken elevator at 1015 N Halsted St?

Use the report form at https://www.elevatoruptime.com/report. It takes about 15 seconds and no account is required.

## Report or correct

- **Report a broken elevator or escalator:** <https://www.elevatoruptime.com/report>
- **Building owner or manager? Claim this listing:** <https://www.elevatoruptime.com/building/d7a11f99-ed95-460d-af40-b0ceed117725#claim> — or email <mailto:info@elevatoruptime.com?subject=Claim%20building%3A%201015%20N%20Halsted%20St%20(d7a11f99-ed95-460d-af40-b0ceed117725)>
- **Elevator service contractor? Claim your devices:** <https://www.elevatoruptime.com/building/d7a11f99-ed95-460d-af40-b0ceed117725#claim-devices> — or send a tip by email <mailto:info@elevatoruptime.com?subject=Contractor%20tip%3A%201015%20N%20Halsted%20St%20(d7a11f99-ed95-460d-af40-b0ceed117725)>

---
Site overview for agents: <https://www.elevatoruptime.com/llms.txt>